. . Especificaciones | . | .
. . Cells Per Unit | . 6 | .
. . Voltage Per Unit | . 12 V | .
. . Capacity | . 7.2 Ah @ 20hr-rate to 1.75V per cell @ 25ºC (77ºF) | .
. . Weight | . Approx. 2.40kg. (5.29 lbs.) | .
. . Maximum Discharge current | . 100A/130A (5sec.) | .
. . Internal Resistance Approx. | . Approx. 23mΩ | .
. . Operating Temperature Range | . Discharge:-15?~50?(5ºF~122ºF) | .
. . | . Charge:-15?~40?(5ºF~104ºF) | .
. . | . Storage:-15?~40?(5ºF~104ºF) | .
. . Nominal Operating Temperature Range | . 25ºC ± 3ºC (77ºF ± 5ºF) | .
. . Float charging voltage | . 13.5 to 13.8 VDC/unit Average at 25ºC (77ºF) | .
. . Recommended Maximum Charging current limit | . 2.16A | .
. . Equalization and Cycle Service | . 14.4 to 15.0 VDC/unit Average at 25ºC (77ºF) | .
. . Self Discharge | . It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25? | .
. . Terminal | . F1/F2-Faston Tab187/250 | .